Note 29

TD TYPE Data Field for the 289 LSS and 289H LSS

In addition to Device Types, which are required for all offices regardless of the type of Cable Pressurization Automatic Monitoring System (CPAMS) used, PressureMAP systems that monitor 289, 289H LSS, 289H-M and Dial-a-Ducers also require that a Transducer Type code is assigned to each device. This code provides additional information required by PressureMAP to perform 289-related monitoring functions. For some Device Types, the PressureMAP editor automatically fills in the required TD Type, and will not allow you to edit that field.

Device Types and Transducer Types are listed in Appendix 1 of the MAP System Data Entry Manual and at the end of the Preface in the Operations Manual.

289 AND 289H RESISTIVE TRANSDUCER TYPES

Pressure—PSI

RP

Standard Resistive Pressure Transducer: 0-9.5 PSI

RP/HP-PSI

High Pressure Resistive Transducer: 5-14.5 PSI

RP/RG-PSI

High Pressure Resistive Transducer: 5-14.5 PSI

RP/RG/HP-PSI

Resistive Pressure Transducer using ring with sheath as ground

RP/TG-PSI

High Pressure Resistive Transducer using ring with sheath as ground

RP/TG/HP-PSI

High Pressure Resistive Transducer using tip with sheath as ground

Pressure—KPA

RP-KPA

Standard Resistive KPA Pressure Transducer: 0-65.5 KPA

RP/HP-KPA

High Pressure Resistive KPA Transducer: 34.48-99.98 KPA

RP/RG-KPA

Resistive KPA Pressure Transducer using ring with sheath as ground

RP/RG/HP-KPA

Resistive KPA Pressure Transducer using ring with sheath as ground

RP/TG-KPA

Resistive KPA Pressure Transducer using tip with sheath as ground

RP/TG/HP-KPA

High Pressure Resistive KPA Transducer using tip with sheath as ground

Flow—SCFH

RF/(range)

Standard Resistive Flow Transducer-9 ranges of SCFH: 0-9.5, 0-19.0, 0-20.0, 0-47.5, 0-50.0, 0-95.0, 0-100.0, 0-185.0, 0-200.0

RF/RG/(range)

Resistive Flow Transducer using ring with sheath as ground-9 ranges of SCFH: 0-9.5, 0-19.0, 0-20.0, 0-47.5, 0-50.0, 0-95.0, 0-100.0, 0-185.0, 0-200.0

RF/TG/(range)

Resistive Flow Transducer using tip with sheath as ground-9 ranges of SCFH: 0-9.5, 0-19.0, 0-20.0, 0-47.5, 0-50.0, 0-95.0, 0-100.0, 0-185.0, 0-200.0

Flow—LPH

RF/(range)

Resistive Flow Transducer-9 ranges of LPH: 0-270, 0-540, 0-570, 0-1350, 0-1420, 0-2700, 0-2830, 0-5380, 0-5670

RF/RG/(range)

Resistive Flow Transducer using ring with sheath as ground-9 ranges of LPH: 0-270, 0-540, 0-570, 0-1350, 0-1420, 0-2700, 0-2830, 0-5380, 0-5670

RF/TG/(range)

Resistive Flow Transducer using tip with sheath as ground-9 ranges of LPH: 0-270, 0-540, 0-570, 0-1350, 0-1420, 0-2700, 0-2830, 0-5380, 0-5670

Contact Alarm

CPAMS_TD

Standard Resistive Contact Alarm

CPAMS_TD/RG

Resistive Contact Alarm using ring with sheath as ground

CPAMS_TD/TG

Resistive Contact Alarm using tip with sheath as ground

AC/115

Contact Alarm for 115V: 540K resistance OK, 270K resistance is ALRM

DRYER

Contact Alarm for 115V: 540K resistance OK, 270K resistance is ALRM (same as AC/115)

AC/230

Contact Alarm for 230V; 540K resistance OK, 270K resistance is ALRM

RR/540K

Contact Alarm; 540K resistance OK, SHRT is ALRM

Other Device Applications

RG/100M

Resistive open pair, monitors the resistance of a pair (Ring/Ground)

RR/100M

Resistive open pair, monitors the resistance of a pair (Tip/Ring)

RT/100M

Resistive open pair, monitors the resistance of a pair (Tip/Ground)

TEMP/212

Thermistor Water Temperature Transducer; range -40 to +212o

TEMP/212/H

Thermistor Air Temperature Transducer; range 32 to 212o



289 AND 289H CURRENT LOOP TRANSDUCER TYPES

Pressure—PSI

CPA/15.0

Current Loop Pressure Transducer, 0-15.0 PSI (absolute)

CPA/30.0

Current Loop Pressure Transducer, 0-30.0 PSI (absolute)

Pressure—KPA

CPA/100.0

Current Loop Pressure Transducer, 0-100.0 KPA (absolute)

CPA/200.0

Current Loop Pressure Transducer, 0-200.0 KPA (absolute)

Flow—SCFH

CF/9.5

Current Loop Flow Transducer, 0-9.5 SCFH

CF/19.0

Current Loop Flow Transducer, 0-19.0 SCFH

CF/47.5

Current Loop Flow Transducer, 0-47.5 SCFH

CF/95.0

Current Loop Flow Transducer, 0-95.0 SCFH

CF/475.0

Current Loop Flow Transducer, 0-475 SCFH

CF/950.0

Current Loop Flow Transducer, 0-950 SCFH

Flow—LPH

CF/270

Current Loop Flow Transducer, 0-270 LPH

CF/540

Current Loop Flow Transducer, 0-540 LPH

CF/1350

Current Loop Flow Transducer, 0-1350 LPH

CF/2700

Current Loop Flow Transducer, 0-2700 LPH

CF/13500

Current Loop Flow Transducer, 0-13500 LPH

CF/27000

Current Loop Flow Transducer, 0-27000 LPH

Other Device Applications

BARO/35

Bi-Directional Flow Transducer, range 0-475 SCFH

BARO/1200

Barometric Pressure Transducer, range 750-1200 millibars

BFTD/475.0

Barometric Pressure Transducer, range 20.6-91.1 inches of Hg

RH/100

Relative Humidity Transducer, range 0%-100% RH

TANK

Tank Volume Transducer, 0-200 cubic ft

EURO_TANK

Tank Pressure Transducer (metric), 0-204 bars

TEMP/167

Temperature Transducer, range 0-167o F

TEMP/75

Temperature Transducer, range 0-75o C

WATER/20

Water Level Transducer, range 0-20.8 inches

WATER/30

Water Level Transducer, range 0-30 feet

289H Voltage Measurement Transducer Types

VAC/TG

AC Voltage, Tip to Ground

VAC/RG

AC Voltage, Ring to Ground

VDC/TG

DC Voltage, Tip to Ground

VDC/RG

DC Voltage, Ring to Ground

VAC/300

AC Voltage, Tip to Ring



289H LSS ADDRESSABLE TRANSDUCER TYPES

Flow—SCFH

AF/9.5

289H Addressable Flow Transducer, 0-9.5 SCFH

AF/19.0

289H Addressable Flow Transducer, 0-19.0 SCFH

AF/47.5

289H Addressable Flow Transducer, 0-47.5 SCFH

AF/95.0

289H Addressable Flow Transducer, 0-95.0 SCFH

AF/475.0

289H Addressable Flow Transducer, 0-475.0 SCFH

AF/950.0

289H Addressable Flow Transducer, 0-950.0 SCFH

Flow—LPH

AF/270

289H Addressable Flow Transducer, 0-270 LPH

AF/540

289H Addressable Flow Transducer, 0-540 LPH

AF/1350

289H Addressable Flow Transducer, 0-1350 LPH

AF/2700

289H Addressable Flow Transducer, 0-2700 LPH

Pressure—PSI

APA

289H Addressable PSI Pressure Transducer, 0-15 PSI (absolute)

Pressure—KPA

APA/KPA

289H Addressable Pressure Transducer, 0-100.0 KPA (absolute)

Dual—Pressure Side

APA/X2

289H Addressable Pressure/Flow Transducer, 0-15.0 PSI (absolute)

APA/KPAX2

289H Addressable Pressure/Flow Transducer, 0-100.0 KPA (absolute)

Dual—Flow Side

AF/9.5X2

289H Addressable Pressure/Flow Transducer, 0-9.5 SCFH

AF/19.0X2

289H Addressable Pressure/Flow Transducer, 0-19.0 SCFH

AF/47.5X2

289H Addressable Pressure/Flow Transducer, 0-47.5 SCFH

AF/95.0X2

289H Addressable Pressure/Flow Transducer, 0-95.0 SCFH

AF/475.0X2

289H Addressable Pressure/Flow Transducer, 0-475.0 SCFH

AF/950.0X2

289H Addressable Pressure/Flow Transducer, 0-950.0 SCFH

AF/270X2

289H Addressable Pressure/Flow Transducer, 0-270 LPH

AF/540X2

289H Addressable Pressure/Flow Transducer, 0-540 LPH

AF/1350X2

289H Addressable Pressure/Flow Transducer, 0-1350 LPH

AF/2700X2

89H Addressable Pressure/Flow Transducer, 0-2700 LPH

Special Addressable Transducers

ABARO/1200

289H Addressable Barometric Pressure Transducer, 750-1200 millibars

ABARO/35

289H Addressable Barometric Pressure Transducer, 20.6-35.0 inches of Hg

AWATER/30

289H Addressable Water Level Transducer, 0-30 feet



CHATLOS ADDRESSABLE TRANSDUCER TYPES

Flow—SCFH

AF/C9.5

Chatlos Addressable Flow Transducer, 0-9.5 SCFH

AF/C5/9.5

Chatlos 5-Bank Addressable Flow Transducer, 0-9.5 SCFH

AF/C10/9.5

Chatlos 10-Bank Addressable Flow Transducer, 0-9.5 SCFH

AF/C19.0

Chatlos Addressable Flow Transducer, 0-19.0 SCFH

AF/C5/19.0

Chatlos 5-Bank Addressable Flow Transducer, 0-19.0 SCFH

AF/C10/19.0

Chatlos 10-Bank Addressable Flow Transducer, 0-19.0 SCFH

AF/C47.5

Chatlos Addressable Flow Transducer, 0-47.5 SCFH

AF/C5/47.5

Chatlos 5-Bank Addressable Flow Transducer, 0-47.5 SCFH

AF/C10/47.5

Chatlos 10-Bank Addressable Flow Transducer, 0-47.5 SCFH

AF/C50.0

Chatlos Addressable Flow Transducer, 0-50.0 SCFH

AF/C5/50.0

Chatlos 5-Bank Addressable Flow Transducer, 0-50.0 SCFH

AF/C10/50.0

Chatlos 10-Bank Addressable Flow Transducer, 0-50.0 SCFH

AF/C95.0

Chatlos Addressable Flow Transducer, 0-95.0 SCFH

AF/C5/95.0

Chatlos 5-Bank Addressable Flow Transducer, 0-95.0 SCFH

AF/C10/95.0

Chatlos 10-Bank Addressable Flow Transducer, 0-95.0 SCFH

AF/C100.0

Chatlos Addressable Flow Transducer, 0-100.0 SCFH

AF/C5/100.0

Chatlos 5-Bank Addressable Flow Transducer, 0-100.0 SCFH

AF/C10/100.0

Chatlos 10-Bank Addressable Flow Transducer, 0-100.0 SCFH

Flow—LPH

AF/C270

Chatlos Addressable Flow Transducer, 0-270 LPH

AF/C5/270

Chatlos 5-Bank Addressable Flow Transducer, 0-270 LPH

AF/C10/270

Chatlos 10-Bank Addressable Flow Transducer, 0-270 LPH

AF/C540

Chatlos Addressable Flow Transducer, 0-540 LPH

AF/C5/540

Chatlos 5-Bank Addressable Flow Transducer, 0-540 LPH

AF/C10/540

Chatlos 10-Bank Addressable Flow Transducer, 0-540 LPH

AF/C1350

Chatlos Addressable Flow Transducer, 0-1350 LPH

AF/C5/1350

Chatlos 5-Bank Addressable Flow Transducer, 0-1350 LPH

AF/C10/1350

Chatlos 10-Bank Addressable Flow Transducer, 0-1350 LPH

AF/C1420

Chatlos Addressable Flow Transducer 0-1420 LPH

AF/C5/1420

Chatlos 5-Bank Addressable Flow Transducer 0-1420 LPH

AF/C10/1420

Chatlos 10-Bank Addressable Flow Transducer 0-1420 LPH

AF/C2700

Chatlos Addressable Flow Transducer, 0-2700 LPH

AF/C5/2700

Chatlos 5-Bank Addressable Flow Transducer, 0-2700 LPH

AF/C10/2700

Chatlos 10-Bank Addressable Flow Transducer, 0-2700 LPH

AF/C2830

Chatlos Addressable Flow Transducer, 0-2830 LPH

AF/C5/2830

Chatlos 5-Bank Addressable Flow Transducer, 0-2830 LPH

AF/C10/2830

Chatlos 10-Bank Addressable Flow Transducer, 0-2830 LPH

Pressure—PSI

AP/C

Chatlos Addressable PSI Pressure Transducer

AP/C5

Chatlos 5-Bank Addressable PSI Pressure Transducer

AP/C10

Chatlos 10-Bank Addressable PSI Pressure Transducer

AP/CH-PSI

Chatlos Addressable PSI High Pressure Transducer

AP/C5/H-PSI

Chatlos 5/10-Bank Addressable PSI High Pressure Transducer

Pressure—KPA

AP/C-KPA

Chatlos Addressable KPA Pressure Transducer

AP/C5/KPA

Chatlos 5/10-Bank Addressable KPA Pressure Transducer

AP/CH-KPA

Chatlos Addressable KPA High Pressure Transducer

AP/C5/H-KPA

Chatlos 5/10-Bank Addressable KPA High Pressure Transducer



UAMC ADDRESSABLE TRANSDUCER TYPES

Pressure

AP/I

Inelcom Addressable mbar Pressure Transducer

AP/L

Lancier Addressable mbar Pressure Transducer

AP/M

Microsol Addressable mbar Pressure Transducer

AP/N

Nicotra Addressable mbar Pressure Transducer

AP/S730

Sparton Addressable mbar Pressure Transducer, 0-10 PSI

AP/S734

Sparton Addressable mbar Pressure Transducer, 0-14.5 PSI

Flow

AF/S9.5

Sparton Addressable SCFH Flow Transducer, 0-9.5 SCFH

AF/S20

Sparton Addressable SCFH Flow Transducer, 0-20 SCFH

AF/S50

Sparton Addressable SCFH Flow Transducer, 0-50 SCFH

AF/S100

Sparton Addressable SCFH Flow Transducer, 0-100 SCFH



DIAL-A-DUCER TRANSDUCER TYPES

Flow—SCFH

DF/9.5

Flow Transducer, 0-9.5 SCFH

DF/19.0

Flow Transducer, 0-19.0 SCFH

DF/47.5

Flow Transducer, 0-47.5 SCFH

DF/95.0

Flow Transducer, 0-95.0 SCFH

DF/475.0

Flow Transducer, 0-475.0 SCFH

DF/950.0

Flow Transducer, 0-950.0 SCFH

Flow—LPH

DF/270

Flow Transducer, 0-270 LPH

DF/540

Flow Transducer, 0-540 LPH

DF/1350

Flow Transducer, 0-1350 LPH

DF/2700

Flow Transducer, 0-2700 LPH

DF/13500

Flow Transducer, 0-13500 LPH

DF/27000

Flow Transducer, 0-27000 LPH

Pressure—PSI

DP/15.0

Pressure Transducer, gauge type

Pressure—KPA

DP/100.0

Pressure Transducer, gauge type

Other Device Applications

DT/167

Fahrenheit Temperature Transducer, (FT device type)

DI

Digital Input (CA device type); support the following values:
- 0x0 -> Logical 0
- 0xF -> Logical 1

For additional information regarding Transducer Type coding, call System Studies at (800) 247-8255 or (831) 475-5777, or email your request to Technical Support.

If you are interested in learning more about System Studies products, please contact us. We are ready to assist you in gaining a much tighter control of your valuable outside plant investment.


© 1996-2008 System Studies Inc. All rights reserved.
(800) 247-8255 | (831) 475-5777