![]() |
|
![]() |
Flow Finder Tip #6July 31, 2006 |
|
Ideally, the average flow being measured should fall within the mid-range of the Flow Finder being installed. However, thanks to the "times two" button located on top of the Flow Gaugethe tool used to manually measure Flow Finder readingsdetermining flow rates that exceed the Flow Finder's range isn't a problem. For example, let's say that a 019 SCFH Flow Finder is installed at an air pipe manifold (or in the incoming port of a Flow Finder Manifold). A flow reading taken with the Flow Gauge is "pegged" (showing the maximum flow rate on the gauge). Depressing the "times two" button in this case drops the needle position back into the reading range, let's say to 12 SCFH. Multiplying the 12 SCFH by two allows the true and accurate flow range of 24 SCFH to be measured.
Reading problems may be encountered when a Flow Finder is installed that accommodates a
significantly higher flow rate than the flow being measured. This problem is attributed to
the non-linear design of the Flow Gauge. Reading the Flow Gauge is as simple as matching the
color of the Flow Finder with the color on the face of the Flow Gauge. For example, a 47.5
SCFH Flow Finder has a blue label. Therefore, the blue scale on the Flow Gauge is used to
determine the flow rate. By examining the face of the Flow Gauge (see image below), you can
see that the numerical increments are different for each flow range. If a 47.5 SCFH Flow
Finder were used to measure a flow of 3 SCFH, for example, it would be very difficult to
determine an accurate reading due to the smaller increments associated with a 47.5 SCFH
Flow Finder. A better method of measuring lower amounts of flow would be to use a 19 SCFH
Flow Finder. This device enables you to use the red scale, which shows a much clearer
distinction between measurements (flow rates). In any case, keep in mind that it is very
difficult to read flows accurately in the lower 10% of any of the Flow Finder ranges.
![]() Flow Range Recommendations For each of the hardware and equipment locations listed below, we have recommended the most appropriate Flow Finder to install. If a flow transducer is currently monitoring air flow at any of these locations, either a Flow Finder with the same range should be installed or you may wish to replace the older resistive transducer with a System Studies Manifold Monitoring assembly of the required range. The Manifold Monitoring Assembly contains a 420 milliamperes (mA) High Resolution Flow or Dual (pressure/flow) Transducer and a Flow Finder Manifold installed on a stainless steel bracket (see the Hardware Products section of this site for more information).
Hopefully, these examples have clarified what Flow Finder ranges are most suitable for
various applications. With any of these suggestions, however, the bottom line is experience.
Like anything else, a little experience goes a long way in determining the best range of
Flow Finder to install in a particular situation. If Flow Finders are a fairly new addition
to your air pressure system, or if you'd just like to find out more about them, please
give us a call (800) 247-8255. |
|
© 1996-2008 System Studies Inc. All rights reserved. |
|